| Date | Status | Code | Description | Ref | Location | Comments |
| 8/8/2013 | Transfer | EF1 | Correct Below | | | |
| 8/8/2013 | Transfer | EF1 | Correct Below | | na | provide muni approved pland |
| 8/8/2013 | Transfer | EF1 | Correct Below | | lobby area | show third party listing on all lights |
| 8/8/2013 | Transfer | EF1 | Correct Below | | at counter | refer undercounter marked-max overcurent 15 amps |
| 8/8/2013 | Transfer | EF1 | Correct Below | | freezer behind counter | ground prong broken off plug atfreezer |
| 8/8/2013 | Transfer | EF1 | Correct Below | | behind counter | all receptacles behind counter must be GFCI protected - including recptacles on wall behind counter |
| 8/8/2013 | Transfer | EF1 | Correct Below | | both panels | panel schedules need more detail - not two circuits labeled alike |
| 8/8/2013 | Transfer | EF1 | Correct Below | | at oven in south space | show third party listing on oven, disconnect required within sight |
| 8/8/2013 | Transfer | EF1 | Correct Below | | in south space | counter be south entry not permitted to be cord connected, use chapter three wiring method |
| 8/8/2013 | Transfer | EF1 | Correct Below | | in back room (high) | provide access to water heater (disconnect required within sight) |