Inspection #: 246758
Inspection Type: Final Electrical
Inspector: D.Rooney
Result: Correction
Comment: call 441-5525, Craig Ketchum to assure door is unlocked before going. Requested by: Jeff Summerville 250-0313

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/8/2013TransferEF1Correct Below   
8/8/2013TransferEF1Correct Below naprovide muni approved pland
8/8/2013TransferEF1Correct Below lobby areashow third party listing on all lights
8/8/2013TransferEF1Correct Below at counterrefer undercounter marked-max overcurent 15 amps
8/8/2013TransferEF1Correct Below freezer behind counterground prong broken off plug atfreezer
8/8/2013TransferEF1Correct Below behind counterall receptacles behind counter must be GFCI protected - including recptacles on wall behind counter
8/8/2013TransferEF1Correct Below both panelspanel schedules need more detail - not two circuits labeled alike
8/8/2013TransferEF1Correct Below at oven in south spaceshow third party listing on oven, disconnect required within sight
8/8/2013TransferEF1Correct Below in south spacecounter be south entry not permitted to be cord connected, use chapter three wiring method
8/8/2013TransferEF1Correct Below in back room (high)provide access to water heater (disconnect required within sight)