Inspection #: 2415
Inspection Type: Electrical Inspection
Inspector: M.Curry
Result: Correction
Comment: electric service change temporarily approved, tag #26811 call for reinspect: 1) bond gec to water line conductor to j box next to service. extend this conductor to service using copper c or cadweld. 2) make equipment ground wire connection to j-box next to service. 3) make sure gec to ground rops is not spliced improperly michael green