Inspection #: 236598
Inspection Type: Electrical Rough
Inspector: D.Rooney
Result: Partial
Comment: Rough In for pan deck conduits

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/11/2013Transfer01See inspection comments Grid lines 1-12/ A-CRough in this area OK to cover
4/11/2013Transfer10110. 15 High-Leg Marking<P><FONT size=2>4-wire delta system: conductor having the higher voltage to ground must be marked orange</FONT> <BR></P>3rd floor electrical room:panel 3Bphases to new feeder not identified properly
4/11/2013Transfer15110. 26(A)(3) Working Clearance height<TABLE style="WIDTH: 345pt; BORDER-COLLAPSE: collapse" border=0 cellSpacing=0 cellPadding=0 width=460 x:str><FONT size=2>6ft-6in from floor or grade</FONT><BR> <TBODY></TBODY></TABLE>2nd floor electrical room:above H panelduct work in work space
4/11/2013Transfer19110. 26(F)(1)(a) DedIcated Space for electrical equipment<FONT size=2>Space equal to width and depth of equipment from floor to 6ft<SPAN style="mso-spacerun: yes">&nbsp; </SPAN>above equipment shall be dedicated to the electrical installation</FONT>Electrical room 1st Flooor:Panel Agutter under panel more than 6"
4/11/2013Transfer5110. 11 Deteriorating AgentsNo use of conductors, equipment in damp or wet locations; in deteriorating gasses, fumes, vapors, etc; at excessive temps1st floor electrical room:underground service entrance conductors not approved for wet location 