| Date | Status | Code | Description | Ref | Location | Comments |
| 4/11/2013 | Transfer | 01 | See inspection comments | | Grid lines 1-12/ A-C | Rough in this area OK to cover |
| 4/11/2013 | Transfer | 15 | 110. 26(A)(3) Working Clearance height | <TABLE style="WIDTH: 345pt; BORDER-COLLAPSE: collapse" border=0 cellSpacing=0 cellPadding=0 width=460 x:str><FONT size=2>6ft-6in from floor or grade</FONT><BR>
<TBODY></TBODY></TABLE> | 2nd floor electrical room:above H panel | duct work in work space |
| 4/11/2013 | Transfer | 19 | 110. 26(F)(1)(a) DedIcated Space for electrical equipment | <FONT size=2>Space equal to width and depth of equipment from floor to 6ft<SPAN style="mso-spacerun: yes"> </SPAN>above equipment shall be dedicated to the electrical installation</FONT> | Electrical room 1st Flooor:Panel A | gutter under panel more than 6" |