Inspection #: 236280
Inspection Type: Undergound Electrical
Inspector: R.Thornton
Result: Correction
Comment: Test not for inspection Requested by: Rick Thornton 343-8316 thorntonrw@muni.org Requested by: Bill Hobbins 350-8395 bhobbins@alcanelectric.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/11/2013Transfer10110. 15 High-Leg Marking<P><FONT size=2>4-wire delta system: conductor having the higher voltage to ground must be marked orange</FONT> <BR></P>3rd floor electrical room:panel 3Bphases to new feeder not identified properly
4/11/2013Transfer5110. 11 Deteriorating AgentsNo use of conductors, equipment in damp or wet locations; in deteriorating gasses, fumes, vapors, etc; at excessive temps1st floor electrical room:underground service entrance conductors not approved for wet location 
4/9/2013Transfer1090. 4 Special Permission<FONT size=2>AHJ's ability to waive specific requirements of NEC where equivalent objectives and safety can be maintained.</FONT>111:222333
4/9/2013Transfer1090. 4 Special Permission<FONT size=2>AHJ's ability to waive specific requirements of NEC where equivalent objectives and safety can be maintained.</FONT>11:2266
3/29/2013Transfer10110. 15 High-Leg Marking<P><FONT size=2>4-wire delta system: conductor having the higher voltage to ground must be marked orange</FONT> <BR></P>location field, correction page:LoC info fiels, correction pagecommens, correction page
3/29/2013Transfer13110. 26(A)(1) WorkClear: Depth<FONT size=2>0-150V: 3'.151-600V condition 1: 3'. 151-600V condition 2: 3'-6". 151-600V condition 3: 4'</FONT>3-29a:3-29b3-29c