| Date | Status | Code | Description | Ref | Location | Comments |
| 4/11/2013 | Transfer | 10 | 110. 15 High-Leg Marking | <P><FONT size=2>4-wire delta system: conductor having the higher voltage to ground must be marked orange</FONT> <BR></P> | 3rd floor electrical room:panel 3B | phases to new feeder not identified properly |
| 4/11/2013 | Transfer | 5 | 110. 11 Deteriorating Agents | No use of conductors, equipment in damp or wet locations; in deteriorating gasses, fumes, vapors, etc; at excessive temps | 1st floor electrical room:underground service entrance conductors not approved for wet location | |
| 4/9/2013 | Transfer | 1 | 090. 4 Special Permission | <FONT size=2>AHJ's ability to waive specific requirements of NEC where equivalent objectives and safety can be maintained.</FONT> | 111:222 | 333 |
| 4/9/2013 | Transfer | 1 | 090. 4 Special Permission | <FONT size=2>AHJ's ability to waive specific requirements of NEC where equivalent objectives and safety can be maintained.</FONT> | 11:22 | 66 |
| 3/29/2013 | Transfer | 10 | 110. 15 High-Leg Marking | <P><FONT size=2>4-wire delta system: conductor having the higher voltage to ground must be marked orange</FONT> <BR></P> | location field, correction page:LoC info fiels, correction page | commens, correction page |
| 3/29/2013 | Transfer | 13 | 110. 26(A)(1) WorkClear: Depth | <FONT size=2>0-150V: 3'.151-600V condition 1: 3'. 151-600V condition 2: 3'-6". 151-600V condition 3: 4'</FONT> | 3-29a:3-29b | 3-29c |