| Date | Status | Code | Description | Ref | Location | Comments |
| 3/29/2013 | Transfer | Correct service item below | * | | | aic rating on breaker |
| 3/29/2013 | Transfer | Correct service item below | * | | | placards at disconnects |
| 3/29/2013 | Transfer | Correct service item below | * | | | |
| 3/29/2013 | Transfer | ES1 | Correct Below | see inspectors comment | Service | CEA XFMR feeding meter main is 480/277V. Meter main and breaker are rated 240V max. |
| 3/29/2013 | Transfer | ES1 | Correct Below | see inspectors comment | All disconnects on parking structure. | Need to be placcarded per 225.37. |
| 3/29/2013 | Transfer | ES1 | Correct Below | see inspectors comment | Parking structure disconnect. | Rated only 240V max. 480V feeder circuit. |
| 3/29/2013 | Transfer | ES1 | Correct Below | see inspectors comment | Stainless gutter | Put on cover. |