Inspection #: 234605
Inspection Type: Service
Inspector: M.Green
Result: Correction
Comment: 9:00 AM Requested by: Jeff 947-1982

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/28/2013TransferCorrect service item below*  aic rating on breaker
3/28/2013TransferCorrect service item below*  placards at disconnects
3/28/2013TransferCorrect service item below*   
3/28/2013TransferES1Correct Belowsee inspectors commentServiceCEA XFMR feeding meter main is 480/277V. Meter main and breaker are rated 240V max.
3/28/2013TransferES1Correct Belowsee inspectors commentAll disconnects on parking structure.Need to be placcarded per 225.37.
3/28/2013TransferES1Correct Belowsee inspectors commentParking structure disconnect.Rated only 240V max. 480V feeder circuit.
3/28/2013TransferES1Correct Belowsee inspectors commentStainless gutterPut on cover.