Inspection #: 231289
Inspection Type: Final Electrical
Inspector: V.Fosberg
Result: Correction
Comment: call 1 hour b4 to meet Requested by: John 232-2561

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/15/2013TransferEF1Correct Below LTE cabinet.Does not have 3rd party listing.
7/15/2013TransferEF1Correct Below Battery charger.Rating sticker shows 47A load. Panel sched shows only 5.64KW per leg. Is this correct? Total load on 100A panel is shown as approx 90A when only 5.64 KW calculated.