Inspection #: 230577
Inspection Type: Final Electrical
Inspector: D.Rooney
Result: Approved
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/25/2013 EF1Correct Below FrontSign circuit cannot feed EM lights.
2/25/2013 EF1Correct Below CeilingEM / exit lights must be on same circuit as normal lights.
2/25/2013 EF1Correct Below Oven hoodPizza conveyor receptacle needs to be GFCI.
2/25/2013 EF1Correct Below POS counterReceptacles need to be GFCI.
2/25/2013 EF1Correct Below Soft drink dispensor.Where is listing label?
2/25/2013 EF1Correct Below Above panel.GFCI protect receptacle.