Inspection #: 229262
Inspection Type: Final Mechanical
Inspector: J.Gadomski
Result: Correction
Comment: AM please Call Keith 30 min. Prior For Entry Requested by: Keith 242-3413

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/11/2013TransferMechFinalSee commentsSee Inspector CommentsTF-1:Above freezerCannot dicharge into a R/A Plenum
6/11/2013TransferMechFinalSee commentsSee Inspector CommentsKitchenRefrigeration has not been inspected
6/11/2013TransferMechFinalSee commentsSee Inspector CommentsTenant SpaceHVAC was not inspected at rough-in. Remove ceiling tiles & provide a ladder for inspection.
6/11/2013TransferMechFinalSee commentsSee Inspector CommentsTenant SpaceKSK did not perform any mechanical work on this job, the permits MUST be obtained by the contractor that performed the work.
6/11/2013TransferMechFinal9Combustibles in Return AirCombustibles are not allowed in the return air plenum IMC 602.2.1Ceiling - throughout - PVC/ABS 