| Date | Status | Code | Description | Ref | Location | Comments |
| 6/11/2013 | Transfer | MechFinal | See comments | See Inspector Comments | TF-1:Above freezer | Cannot dicharge into a R/A Plenum |
| 6/11/2013 | Transfer | MechFinal | See comments | See Inspector Comments | Kitchen | Refrigeration has not been inspected |
| 6/11/2013 | Transfer | MechFinal | See comments | See Inspector Comments | Tenant Space | HVAC was not inspected at rough-in. Remove ceiling tiles & provide a ladder for inspection. |
| 6/11/2013 | Transfer | MechFinal | See comments | See Inspector Comments | Tenant Space | KSK did not perform any mechanical work on this job, the permits MUST be obtained by the contractor that performed the work. |
| 6/11/2013 | Transfer | MechFinal9 | Combustibles in Return Air | Combustibles are not allowed in the return air plenum IMC 602.2.1 | Ceiling - throughout - PVC/ABS | |