Inspection #: 227416
Inspection Type: Final Electrical
Inspector: D.Rooney
Result: Correction
Comment: FINAL INSPECTION PLEASE FOR CORRECTIONS. CALL tED PRIOR TO VISIT AT 229-0453 Requested by: Dave 349-9668 dhouse@ravenelectric.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/31/2013TransferEF1Correct Below thoroughoutEmployees may not occupy workspaces until a certificate of occupancy or conditional certificate of occupancy is issued
1/31/2013TransferEF1Correct Below 2nd floorallreceptacles must have final inspection before modular furniture is installed
1/31/2013TransferEF1Correct Below 2nd floorceiling inspectioin required where modular walls are ceiling fed
1/31/2013TransferEF1Correct Below 2nd floormodular walls must be listed assemblies or be installed per NEC (support for flexible metala conduit
1/31/2013TransferEF1Correct Below breakroomGFI receptacles for vending machines need to be readily accessible