Inspection #: 213026
Inspection Type: Final Electrical
Inspector:
Result:
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/16/2012 EF1Correct Below Bar area orangew recept for receipt printer and TV recept not GFCI protected. 
10/16/2012 EF1Correct Below Break room recepts need GFCI (floor drain and contiguous with kitchen). 
10/16/2012 EF1Correct Below update panel schedules: make each circuit designation unique. 
10/16/2012 EF1Correct Below Roof top items: could not find priors. 
10/16/2012 EF1Correct Below Dishwasher fed from (2) circuits: No disconnects at machine. No marked off on appliance. No placcarding to show (2) sources of power. 
10/16/2012 EF1Correct Below Remote exterior heads. 
10/16/2012 EF1Correct Below Exterior landscape lighting, etc. 