Click Here To View Another Inspection Inspection #: 210164 Inspection Type: Undergound Electrical Inspector: H8 Result: Partial Comment: Requested by: Bill Hobbins 350-8395 bhobbins@alcanelectric.com 1. Elevator pit M-4: 3/0 CU GEC cadwelded to elevator casing and run through slab to col M-4. 2. #3/0 CU GEC from col F-2 to MDP underslab. 3. Short GRC stubs into lift station LS-1. Same at LS-2. 4.Hydro pit control conduits at south end of pit: short conduit runs to panel OSD2. NOTE: GEC's run to MDP in bsmt. Is this where the main service OCPD is located? Inspection Corrections DateStatusCodeDescriptionRefLocationComments