Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 208418
Inspection Type: Final Electrical
Inspector: M.Green
Result: Partial
Comment: Requested by: ken Smith 440-0005 frank@alyeskaelectric.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/1/2012TransferEF1Correct Below Bar area orangew recept for receipt printer and TV recept not GFCI protected. 
10/1/2012TransferEF1Correct Below Break room recepts need GFCI (floor drain and contiguous with kitchen). 
10/1/2012TransferEF1Correct Below update panel schedules: make each circuit designation unique. 
10/1/2012TransferEF1Correct Below Roof top items: could not find priors. 
10/1/2012TransferEF1Correct Below Dishwasher fed from (2) circuits: No disconnects at machine. No marked off on appliance. No placcarding to show (2) sources of power. 
10/1/2012TransferEF1Correct Below Remote exterior heads. 
10/1/2012TransferEF1Correct Below Exterior landscape lighting, etc. 
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter