Inspection #: 203323
Inspection Type: Ceiling Rough Electrical
Inspector: V.Fosberg
Result: Partial
Comment: Electrical ceiling inspection for Tuesday Afternoon - Sept 4 - Olive Garden - Dimond Mall - Site Contact Tommy Meade Cell Phone 907-232-9213 Requested by: Nina Mann 907-770-7913 nina@alyeskaelectric.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/5/2012Transfercorrection for Ceiling below*   
9/5/2012TransferEC1Correct Below Gas line at RTU 1 violates working clearances. May build 30" x 36" treated wood platform to provide level working space. 
9/5/2012TransferEC1Correct Below Labelling for mushroom head fans, MAU, ref equipment. 
9/5/2012TransferEC1Correct Below Trash room ref equipment fused disconnect needs to move out to strut for working clearances. 