Inspection #: 202495
Inspection Type: Ceiling Rough Electrical
Inspector: M.Green
Result: Partial
Comment: . Requested by: Tommy Meade 232-9213 frank@alyeskaelectric.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/29/2012Transfercorrection for Ceiling below*   
8/29/2012TransferEC1Correct Below Gas line at RTU 1 violates working clearances. May build 30" x 36" treated wood platform to provide level working space. 
8/29/2012TransferEC1Correct Below Labelling for mushroom head fans, MAU, ref equipment. 
8/29/2012TransferEC1Correct Below Trash room ref equipment fused disconnect needs to move out to strut for working clearances. 