Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 198823
Inspection Type: Electrical Rough
Inspector: H8
Result: Partial
Comment: Please call when in route. Thank you. Requested by: Carson 301-3877 walls ok

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
       
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS