Inspection #: 195862
Inspection Type: Final Electrical
Inspector: H8
Result: Partial
Comment: Call Justin Half Hour Before 306-3020 Requested by: Justin Morgan 907-306-3020 justin@supremeelectricak.com Requested by: Justin Morgan 306-3020 Justin@supremeelectricak.com Escalators 2A & 2B, 3A & 3B: Conditional electrical final approved until 2-1-2013. Conditional electrical final for escalators 1A & 1B extended until 2-1-2013. Complete, correct, resolve: 1) Change 60A main breakers to 50A, and fuses for individual escalators to 30A. 2) Pit lts, recepts, seismic switches to be fed from new sub panel in machine room( RFI outstanding). 3) Machine room disconnects need permanent labelling.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
       