Inspection Type: Final Electrical
Inspector: D.Rooney
Result: Approved
Comment: please call ahead 15 minutes. Requested by: kelly wilmes 227 8625 safetway @acsalaska.net

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/15/2012 EF1Correct Below vfd workspace at penthouse 
8/15/2012 ElecRoughOther000 Electrical Rough OtherPlease correct the following:Conditional electrical final approved until 8-15-2012. 
8/15/2012 ElecRoughOther000 Electrical Rough OtherPlease correct the following:Parking lot light poles not completed. 
8/15/2012 ElecRoughOther000 Electrical Rough OtherPlease correct the following:Penthouse VFD's need placcarding due to impropper working clearances. 
8/15/2012 EF1Correct Below placards at service 
8/15/2012 EF1Correct Below panel schedules incomplete (all floors) 
8/15/2012 EF1Correct Below em lights at center row first floor have no power 
8/15/2012 EF1Correct Below heat trace incomplete 
8/15/2012 EF1Correct Below north and west lightpoles incomplete 
8/15/2012 EF1Correct Below no power ar west parking lot gfcis 
7/10/2012 EF1Correct Below Mechanical room -:lighting contactor 
7/10/2012 EF1Correct Below Mechanical room:between boilers 
7/10/2012 EF1Correct Below Mechanical room:far right corner 