Inspection #: 191869
Inspection Type: Final Electrical
Inspector: D.Rooney
Result: Partial
Comment: Corrections to previous finals. Should be averything except radiology and mammogram. Would like CCO.. Requested by: Curt Birch 232-8778 curt@qealaska.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/31/2012TransferEF1Correct Below Boiler roomController for pumps 4, 5 and 11 are too big. Controollers only suitable for 6amps or more and pumps are rated less that 3 amps.
7/31/2012TransferEF1Correct Below In server roomOutlets for server racks are not yet installed.
7/31/2012TransferEF1Correct Below Boiler roomPumps 9 and 11 do not appear to have a third parts liisting.
7/31/2012TransferEF1Correct Below Pod Bcord installed for scale not permitted inside wall
7/31/2012TransferEF1Correct Below Boiler roomSome disconnects/motor controllers need bonnding bushings at knockouts.
7/31/2012TransferElecRoughOther000 Electrical Rough OtherPlease correct the following:Provide latest approved dwgs/change orders 
7/31/2012TransferElecRoughOther000 Electrical Rough OtherPlease correct the following:Genset shown on dwgs as 1200A. Actual installation is 800A genset. MDP load calc is over 900A. Dwgs need to doccument solution. 
7/31/2012TransferElecRoughOther000 Electrical Rough OtherPlease correct the following:  
7/31/2012TransferElecRoughOther000 Electrical Rough OtherPlease correct the following:Verify 4-pole ATS. (genset gnd and neut. bonded) 
7/31/2012TransferElecRoughOther000 Electrical Rough OtherPlease correct the following:Verify GFP service disconnect in ATS. 
7/31/2012TransferElecRoughOther000 Electrical Rough OtherPlease correct the following:Check 110.26 working clearances for 1st fl electric room. 
7/31/2012TransferElecRoughOther000 Electrical Rough OtherPlease correct the following:Do approved dwgs show genset as Art. 702? 