Inspection #: 190299
Inspection Type: Final Electrical
Inspector: O.Burbridge
Result: Correction
Comment: . Requested by: kelly wilmes 2278625

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/10/2012TransferEF1Correct Below Mechanical room -:lighting contactor 
7/10/2012TransferEF1Correct Below Mechanical room:between boilers 
7/10/2012TransferEF1Correct Below Mechanical room:far right corner 
7/10/2012TransferEF1Correct Below vfd workspace at penthouse 
7/10/2012TransferEF1Correct Below no power ar west parking lot gfcis 
7/10/2012TransferEF1Correct Below north and west lightpoles incomplete 
7/10/2012TransferEF1Correct Below heat trace incomplete 
7/10/2012TransferEF1Correct Below em lights at center row first floor have no power 
7/10/2012TransferEF1Correct Below panel schedules incomplete (all floors) 
7/10/2012TransferEF1Correct Below placards at service 