Inspection #: 189769
Inspection Type: Final Electrical
Inspector: D.Rooney
Result: Partial
Comment: . Requested by: kelly wilmes 2278625 . Requested by: kelly wilmes 2278625

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/6/2012TransferEF1Correct Below Mechanical room -:lighting contactorhot and switch-leg (or neutral) must pass through same conduit nipple
7/6/2012TransferEF1Correct Below Mechanical room:between boilerstwo pumps not within sight of controller or breaker
7/6/2012TransferEF1Correct Below Mechanical room:far right cornerVFDs do not have required working clearances