| Date | Status | Code | Description | Ref | Location | Comments |
| 7/13/2012 | Transfer | ElecRoughOther | 000 Electrical Rough Other | Please correct the following: | Provide latest approved dwgs/change orders | |
| 7/13/2012 | Transfer | ElecRoughOther | 000 Electrical Rough Other | Please correct the following: | Genset shown on dwgs as 1200A. Actual installation is 800A genset. MDP load calc is over 900A. Dwgs need to doccument solution. | |
| 7/13/2012 | Transfer | ElecRoughOther | 000 Electrical Rough Other | Please correct the following: | | |
| 7/13/2012 | Transfer | ElecRoughOther | 000 Electrical Rough Other | Please correct the following: | Verify 4-pole ATS. (genset gnd and neut. bonded) | |
| 7/13/2012 | Transfer | ElecRoughOther | 000 Electrical Rough Other | Please correct the following: | Verify GFP service disconnect in ATS. | |
| 7/13/2012 | Transfer | ElecRoughOther | 000 Electrical Rough Other | Please correct the following: | Check 110.26 working clearances for 1st fl electric room. | |
| 7/13/2012 | Transfer | ElecRoughOther | 000 Electrical Rough Other | Please correct the following: | Do approved dwgs show genset as Art. 702? | |