Inspection #: 184708
Inspection Type: Final Electrical
Inspector: D.Rooney
Result: Partial
Comment: Continue 1st floor final inspection. Call Justin at 223-5447 when arrive. Thanks. Requested by: Curt Birch 232-8778 curt@qealaska.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/27/2012TransferEF1Correct Below Boiler roomController for pumps 4, 5 and 11 are too big. Controollers only suitable for 6amps or more and pumps are rated less that 3 amps.
6/27/2012TransferEF1Correct Below In server roomOutlets for server racks are not yet installed.
6/27/2012TransferEF1Correct Below Boiler roomPumps 9 and 11 do not appear to have a third parts liisting.
6/27/2012TransferEF1Correct Below Pod Bcord installed for scale not permitted inside wall
6/27/2012TransferEF1Correct Below Boiler roomSome disconnects/motor controllers need bonnding bushings at knockouts.