Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 184501
Inspection Type: Final Electrical
Inspector: D.Rooney
Result: Correction
Comment: . Requested by: kelly wilmes 2278625 safetway@acsalaska.net

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/3/2012TransferEF1Correct Below Mechanical room -:lighting contactorhot and switch-leg (or neutral) must pass through same conduit nipple
7/3/2012TransferEF1Correct Below Mechanical room:between boilerstwo pumps not within sight of controller or breaker
7/3/2012TransferEF1Correct Below Mechanical room:far right cornerVFDs do not have required working clearances
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS