Inspection #: 182304
Inspection Type: Final Electrical
Inspector: M.Green
Result: Approved
Comment: AM final inspection requested for Signage approval. Please call Randy 360-3289 to meet on site.. Requested by: Tony Sellen 349-9668 tsellen@ravenelectric.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/14/2012 ElecRoughOther000 Electrical Rough OtherPlease correct the following:Signs needed at service per 702.8 showing: 1) Location & type of alternate power source. 2)Warning about bonding location relative to genset. Use 2011 NEC example. 