Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 181951
Inspection Type: Service
Inspector: R.Thornton
Result: Correction
Comment: Electrical service inspection: Please call the electrical general foreman at 907-299-4159 when traveling to the site so he can meet the inspector. Thank you.. Requested by: Phil Poythress 646-5172 ppoythress@epsinc.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/10/2012TransferES5supply bonding<TABLE style="WIDTH: 285pt; BORDER-COLLAPSE: collapse" border=0 cellSpacing=0 cellPadding=0 width=380 x:str> <COLGROUP> <COL style="WIDTH: 285pt; mso-width-source: userset; mso-width-alt: 13897" width=380> <TBODY> <TR style="HEIGHT: 22.5pt; mso-height-source: userset" height=30> <TD style="BORDER-BOTTOM: #d4d0c8; BORDER-LEFT: #d4d0c8; BACKGROUND-COLOR: transparent; WIDTH: 285pt; HEIGHT: 22.5pt; BORDER-TOP: #d4d0c8; BORDER-RIGHT: #d4d0c8" height=30 width=380><FONT size=2>supply side bonding undersized or not provided</FONT></TD></TR></TBODY></TABLE> increase line side bonds from #2 to 2/0
8/10/2012TransferES1Correct Belowsee inspectors comment remove paint from can below ground lugs
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS