Inspection #: 167294
Inspection Type: Final Electrical
Inspector: M.Green
Result: Partial
Comment: final inspection request, please call Randy Kroon 15 minutes before arriving to meet on site 360-3289.. Requested by: Tony Sellen 349-9668 tsellen@ravenelectricinc.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/1/2012TransferElecRoughOther000 Electrical Rough OtherPlease correct the following:Signs needed at service per 702.8 showing: 1) Location & type of alternate power source. 2)Warning about bonding location relative to genset. Use 2011 NEC example. 