Inspection #: 161991
Inspection Type: Wall Rough Electrical
Inspector: M.Green
Result: Correction
Comment: Wall roughin mammogram room change 2nd floor. Final electrical first floor south as much as time allowed. Call Justin at 223-5447 when arrive. Thanks. . Requested by: Curt Birch 232-8778 curt@qealaska.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/25/2012TransferEW1300. 42commentSee inspectors commentExam rooms: GFCI protection of receptacles within 6 ft of sinks. 
6/25/2012TransferEW1300. 42commentSee inspectors commentOffice cubicles: where is listing mark? 
6/25/2012TransferEW1300. 42commentSee inspectors commentNorth end of office furnature cubicles: some receptacles are dead. 
6/25/2012TransferEW1300. 42commentSee inspectors comment The final comments apply to "Clinical Pod A". 2nd fl mammogram wall rough approved.