Inspection #: 146072
Inspection Type: Final Electrical
Inspector: D.Rooney
Result: Partial
Comment: This is the final cut over from temp to perm service will require us to contact inspector directly, when we are ready for inspection. We are attempting to keep business loss to a minimum. Contact Dave Stevenson 907-351-5163 Requested by: Sandy Eunice 907-351-9339 drselectric@yahoo.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/1/2012TransferEF1Correct Below at step up transformerDisconnect required in secondary conductors within 25 feet
10/1/2012TransferEF1Correct Below Secondary conductorsEngineer needs to update plans to remove neutral conductor from disconnect to panel or contractor needs to install neutral conductor