Inspection #: 110462
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: AM PLZ - Call John @ 903-1009 1/2hr b4 coming to meet for basement only

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/4/2013TransferEF1Correct Below troffersplates not screwed
6/4/2013TransferEF1Correct Below celingboxes cannot be supported by emt
6/4/2013TransferEF1Correct Below blr rmhang lt properly
6/4/2013TransferEF1Correct Below stairno em lt
6/4/2013TransferEF1Correct Below T-bar grid ceilings.SAome troffers need seismic wires.
6/4/2013TransferEF1Correct Below Troffer fixt..Not fastened to grid.
6/4/2013TransferEF1Correct Below T-bar ceilings.MC cable support wires need to tie to grid.
6/4/2013TransferEF1Correct Below Track lightingNeeds supportwires every 4ft.
6/4/2013TransferEF1Correct Below Kitchen ceiling.Complete cord reel or power pole rough-in.
6/4/2013TransferEF1Correct Below Exterior remote EMhead 
6/4/2013TransferEF1Correct Below Double doors to exterior.Remote ext head not coming on.
6/4/2013TransferEF1Correct Below AHUsWhere is listing label?
6/4/2013TransferEF1Correct Below VariousTrim plates missing.
6/4/2013TransferEF1Correct Below pnlproper designations.
6/4/2013TransferEF1Correct Below pnlsub feed breaker not labelled .