Permit Number:
C21-1153
Permit Type:
Commercial Building Permit - None BldgNew
Address:
W 160 48TH AVE Anchorage
Location:
160 W 48th Ave
Work Description:
EPLANS-117094 SQFT, TYPE VB, OCCUPANCY R-1-GJS
NO CCO ON THIS PERMIT UNTIL SHARED ACCESS WITH C15-1806 IS RESOLVED. JCA 6/19/23
**REVOKED MAIN PERMIT AND ISSUED CORE AND SHELL ONLY PER JUDY 6/19/23 - SEE HER COMMENTS UNDER PD CIVIL REVIEW - BWP**
Change order X22-1625 has been approved and this permit (C21-1153) has full PD Civil approval. - RDO (Per PDCivil Final Review)
Status:
Issued
Project Name:
EPLANS- CANDLEWOOD SUITES/HOLIDAY INN EXPRESS
Review Type:
Plumbing
Result:
Correction
Result Date:
9/23/2021 3:26:24 PM
Comments:
Code Section
Review Comment
Status
Advisory Information:
172
5
Plumbing
Leigh Bergstrom
9/23/21 3:05 PM
Changemark
PLUM-1
IF THE POOL SHOP DRAWINGS WERE DOWNLOADED, WE COULD NOT LOCATE THEM. PLEASE CLARIFY THEIR SPECIFIC LOCATION IN THE PLANS OR DOCUMENTS.
M2.2.pdf
Unresolved
173
5
Plumbing
Leigh Bergstrom
9/23/21 3:13 PM
Changemark
PLUM-1
PLEASE INDICATE THE LONGEST RUN IN EACH DIRECTION FROM THE METER TO THE FARTHEST APPLIANCE.
M3.8.pdf
Unresolved
174
5
Plumbing
Leigh Bergstrom
9/23/21 3:13 PM
Changemark
PLUM-2
PLEASE INDICATE THE GAS SUPPLY PRESSURE COMING FROM THE GAS PRESSURE REGULATOR.
M3.8.pdf
Unresolved
175
5
Plumbing
Leigh Bergstrom
9/23/21 3:13 PM
Changemark
PLUM-3
THE GAS RISERS ON THIS SHEET ARE DESIGNATED "A", "B", "C" AND "D". THE GAS RISERS ON M3.7 ARE DESIGNATED "1", "2", "3" AND "4". PLEASE CLARIFY.
M3.8.pdf
Unresolved
176
5
Plumbing
Leigh Bergstrom
9/23/21 3:19 PM
Comment
THE RESPONSE TO COMMENT #141 SAID TO REFER TO SHEET M2.11. WE COULD NOT FIND SHEET #M2.11 OR A SHEET #M2.10. PLEASE CLARIFY.
Unresolved
177
5
Plumbing
Leigh Bergstrom
9/23/21 3:22 PM
Comment
PLUMBING IS APPROVED FOR UNDERGROUND ONLY. 9/23/2021 L.W.B.