Register
My Neighborhood
Jobs
Contact Us
Home
Residents
Businesses
Government
Visitors
Departments
Public Safety
Transportation
Recreation
ePay
Maps
Services A-Z
Muni.org
>
Departments
>
Development Services
> Permit Information & Inspection Request
Click Here To Go Back To Permit Information
Permit Number:
C21-1153
Permit Type:
Commercial Building Permit - None BldgNew
Address:
W 160 48TH AVE Anchorage
Location:
160 W 48th Ave
Work Description:
EPLANS-117094 SQFT, TYPE VB, OCCUPANCY R-1-GJS
NO CCO ON THIS PERMIT UNTIL SHARED ACCESS WITH C15-1806 IS RESOLVED. JCA 6/19/23
**REVOKED MAIN PERMIT AND ISSUED CORE AND SHELL ONLY PER JUDY 6/19/23 - SEE HER COMMENTS UNDER PD CIVIL REVIEW - BWP**
Change order X22-1625 has been approved and this permit (C21-1153) has full PD Civil approval. - RDO (Per PDCivil Final Review)
Status:
Issued
Project Name:
EPLANS- CANDLEWOOD SUITES/HOLIDAY INN EXPRESS
Review Type:
Electrical
Result:
Approved
Result Date:
8/25/2021 3:28:00 PM
Comments:
Code Section
Review Comment
Status
Advisory Information:
The electrical plans are provided and reviewed and approved.
-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
167
4
Electrical
Don Crafts
8/25/21 1:37 PM
Changemark
ELEC #01
Please provide pool area bonding details.
SP.1.pdf
Unresolved
168
4
Electrical
Don Crafts
8/25/21 1:46 PM
Changemark
ELEC #01
Provide properly sized ground electrode conductor details and complete list of grounding electrodes, including UFER (concrete encased electrode). Is there interconnecting building steel serving as an electrode. Structural drawings appear to show that this is not the case.
E4.1.pdf
Unresolved
169
4
Electrical
Don Crafts
8/25/21 3:23 PM
Comment
Please respond to electrical comments (Ref # 167 and Ref # 168) for underground electrical approval in order to support an F & F approval for the entire permit.
ADA Compliance
Privacy Statement & Disclaimer
Employee Search
eNewsletter
RSS
OFFICIAL WEB SITE OF THE MUNICIPALITY OF ANCHORAGE, ALASKA
632 West 6th Avenue, Anchorage, Alaska 99501