Register
My Neighborhood
Jobs
Contact Us
Home
Residents
Businesses
Government
Visitors
Departments
Public Safety
Transportation
Recreation
ePay
Maps
Services A-Z
Muni.org
>
Departments
>
Development Services
> Permit Information & Inspection Request
Click Here To Go Back To Permit Information
Permit Number:
C21-1153
Permit Type:
Commercial Building Permit - None BldgNew
Address:
W 160 48TH AVE Anchorage
Location:
160 W 48th Ave
Work Description:
EPLANS-117094 SQFT, TYPE VB, OCCUPANCY R-1-GJS
NO CCO ON THIS PERMIT UNTIL SHARED ACCESS WITH C15-1806 IS RESOLVED. JCA 6/19/23
**REVOKED MAIN PERMIT AND ISSUED CORE AND SHELL ONLY PER JUDY 6/19/23 - SEE HER COMMENTS UNDER PD CIVIL REVIEW - BWP**
Change order X22-1625 has been approved and this permit (C21-1153) has full PD Civil approval. - RDO (Per PDCivil Final Review)
Status:
Issued
Project Name:
EPLANS- CANDLEWOOD SUITES/HOLIDAY INN EXPRESS
Review Type:
Architectural
Result:
Shell
Result Date:
8/9/2021 4:41:00 PM
Comments:
Code Section
Review Comment
Status
Advisory Information:
Architectural
Don Crafts
8/9/21 2:39 PM
Changemark
ARCH #01
There are 2 exits from the Dining area to this patio space. It appears that this patio space is greater than 750 square feet in area. Unless you can show that the occupant load of this patio space added to the exiting from the dining area is less than 49, please provide a second exit from this patio area. IBC 2015
Architectural
Don Crafts
8/9/21 4:24 PM
Changemark
ARCH #01
The Electrical Plans (E2.1 and E2.2) show adequate Exit signage per the requirements if IBC Section 1013. However, the Electrical Plans (E2.1 and E2.2) do not show adequate Means of Egress Illumination per the requirements if IBC Section 1008, particularly at the Exit Discharges. Please co-ordinate with Electrical.
A111.pdf
A031.pdf
ADA Compliance
Privacy Statement & Disclaimer
Employee Search
eNewsletter
RSS
OFFICIAL WEB SITE OF THE MUNICIPALITY OF ANCHORAGE, ALASKA
632 West 6th Avenue, Anchorage, Alaska 99501