Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C19-1196
Permit Type: Commercial Building Permit - None BldgNew
Address: E 849 DIMOND BLVD Anchorage
Location:
Work Description:

NEW RESTAURANT WITH INDOOR DINING AREA, COMMERCIAL KITCHEN AND DRIVE-THRU LANE - RED

2600 SF - TYPE VB CONST / A-2 OCCUPANCY

Status: Closed
Project Name: RAISING CANE'S
Review Type: Plumbing
Result: Approved
Result Date: 5/28/2019 1:20:36 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:


Reviewed by: Bergstrom, Leigh W.

Phone: 343-8326

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Richard Dienes-Oehm

Phone: 343-8034

Email: Dienes-OehmRE@muni.org

Project: RAISING CAIN'S

Review Number: 429763



1) STATUS: 5-10-2019 Comments to be addressed.                 5-28-2019 APPROVED.


2) The following comments based upon the 2012 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations.                   RESOLVED 5-28-2019.


3) M003                Basic Materials and Methods item #13 instructs the contractor to provide water hammer arrestors and that they are to be sized per the schedule. Please clarify the location of the schedule.                 RESOLVED PER RE-SUBMITTAL RECEIVED 5-28-2019.


4) M100                Clarify the note 3" RL UP (TYP) in the area of the Men's bathroom.                RESOLVED PER RE-SUBMITTAL RECEIVED 5-28-2019.


5) M100                Except for the mop sink, all FD-2's are to be provided with trap seal protection per UPC 1007.1.             RESOLVED PER RE-SUBMITTAL RECEIVED 5-28-2019.


6) M101                Clarify the size and location of the plumbing vent riser through the roof for all of the kitchen area fixtures.               RESOLVED PER RE-SUBMITTAL RECEIVED 5-28-2019.


7) When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature.RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.  (23.10.104.8.1)                  RESOLVED 5-28-2019.

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS