Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C19-1196
Permit Type: Commercial Building Permit - None BldgNew
Address: E 849 DIMOND BLVD Anchorage
Location:
Work Description:

NEW RESTAURANT WITH INDOOR DINING AREA, COMMERCIAL KITCHEN AND DRIVE-THRU LANE - RED

2600 SF - TYPE VB CONST / A-2 OCCUPANCY

Status: Closed
Project Name: RAISING CANE'S
Review Type: Fire
Result: Approved
Result Date: 5/1/2019 9:14:00 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Show address facing Dimond Blvd. 

2_Resolved
Occupants outside of room 142 can not exit through this room. Reconfigure exit signs to direct occupants from the kitchen out to the two exits in the dinning area. Since only two exits are used verify that the two exits on the dinning area satisfy the 1/2/  diagonal distance for two exits in an sprinkled building.   

3_Resolved
E-lights appear to be short in the north east corner of the dinning area. Show additional e- lights in that area to meet the minimum ft candle required. 

4_Resolved
Show the required occupancy placard in the main seating area. 




Advisory Information:

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS