Permit Number: C16-1501
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: TENANT IMPROVEMENT, NEW WALL, FINISHES AND FIXTURES, MECH, ELEC AND PLBG INCLUDED-GJS
CONTRACTOR TO PAY INSPECTION FEES-GJS
***10/10/16 CONTRACTOR PRE-PAID FOR (10) INSPECTIONS.AE****
Status: Closed
Project Name: HOT TOPIC
Review Type: Architectural
Result: Correction
Result Date: 6/20/2016 4:45:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:



Architectural Comments



                                                                



 



Reviewed by: David Abuobaid                                                  Permit #: C15-1501



Phone: 343-8333                                                                       Date:
6/21/2016



Fax:     249-7775



Email:  AbuobaidDH@muni.org



Permit Manager: Bob Parker



Phone: 343-8319



E Email: ParkerRW@muni.org



Project: Hot Topic (Fax:
277-1752)



____________________________________________________________________________



 



1.  The following comments based upon the 2014
International Building Code (IBC) must be resolved before a permit is issued.
The approval of plans and specifications does not permit the violation of any
section of the IBC or any federal, state or local regulations. 



 



2.  CODE ANALYSIS:



Sheet
T. Please address the following:



A:   The adopted international code are all 2012 edition
not 2009 edition.



B    The adopted National Electrical Code is
2014 edition not 2011 edition.



C.   What is the building construction type?



 



3.  REQUIRED EXITING: 



Sheet
A1. The code study shows occupant load of 58 people. Please show on the plans
the two required exits, and the travel distance and the exit doors hardware.    



 



4.
When the above comments have been addressed, please update the plans at the MOA
Plans Review Office with three sets of revised architectural pages to include
clouded changes, engineers stamp and signature. 



         