Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C14-1920
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: INTERIOR ALTERATION OF EXISTING RETAIL SPACE-GJS
Status: Closed
Project Name: KIDS FOOT LOCKER
Review Type: Fire
Result: Correction
Result Date: 9/30/2014 6:27:10 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Fire Plan Review

 

Initial review 9/30/14

 

Review Status:  Comments/corrections

 

Comments:

 

1.  Add sign over entrance doors "these doors to remain unlocked while space is occupied". 

 

2.  IBC 907.2.20 Covered Mall buildings shall have emergency voice evac system.  Dimond Center is currently installing the new system, this space shall have system installed prior to stocking. 

 

3.  Submit fire alarm and sprinkler plans separately for permitting if needed. 

4.  AHU/duct detectors shall report into alarm panel.

 

 

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS