New Comm T/I to include exterior face lift, plumb, mech, and elect - BWP
CCO ISSUED 4/3/2015-GJS
Permit Number C14-1563
Project Name: H&M Core & Shell, Dimond Center, 800 E. Dimond, Suite 3-500
Permit Manager: Bob Parker, 343-8391
Fire Plan Review: Cleo Hill 9907)267-4911
Review Status
8/25/14 3rd Review: Status: Approved C. Hill
8/22/14-2nd review Status: Corrections-meeting scheduled for 8/25/14
unable to locate submittal pages for adding electrical work to roof and mezzanine level.
7/16/14-Initial review
Scope: Core and Shell, electrical and exterior.
General
This review is code compliance review based on the requirements of the International Building and Fire Code, 2009 Edition and adopted MOA and SOA ammendments. this review does not permit the violation of the biloding or fire codes, nor any federal, state or local regulation.
SUMBIT ALL COMMENTS, INFORMATION AND RESPONSES TO YOUR PERMIT MANAGER, NOT TO THE FIRE REVIEWER.
Comments:
8/25/14-All comments addressed and shown on plans. Approved. C. Hill
1. Provide exiting study showing minimum required exiting from tower. Including exiting distance. Blocking off East side exiting could impact minimum exiting requriements. Also show exiting study for mezzanine level with the demo of two stairs. Show and label on plans rated corridors.
2. G1.00, Apparently all exits are not shown from each level. Redo page showing proper exiting for occuplant loads and exiting distance from each level. Also show correct door swing.
3. A1.01. Grid line B btwn 6 and 5, construction barricade. Depending on exiting study, temporary exit doors could be required thru barrier.
4. A1.30, C1 new door @ pool..provide door rating.
5. M002 Atrium smoke control, smoke directing fans. Several have been removed since thjis system was installed. Verify that current configuration meets cfms per 1982 UBC 1807G or better.
6. Provide copy of smoke evacuation annual servicve report. Any deficiencies shall be corrected.
7. Exit signs as shown are appropriate for vacant space. Exit signs shall be reevaluated on Ti submittals. Note only.