PERMIT INFORMATION
Permit Number: C11-1609
Change Order Number: X12-1246
Project Name: Olive Garden Dimond Center
Permit Manager: Tony Barganier | ph: (907) 343-8339 | barganierta@muni.org
Plan Review: Mark Panilo | ph: (907) 343-8081 fax: (907) 249-7679 | panilomm@muni.org
Please submit all information through your Permit Manager.
REVIEW STATUS
04/10/2012 – Initial review (290954). Comments issued.
1. LATERAL RESTRAINT OF ENTRY ROOF
Refer to Sheet S3.2, Detail 17/S4.4. Please clarify the lateral restraint of the high roof at the entry. Given the location and orientation (horizontal and vertical) of the HSS 4x4 struts, it seems that there are no ways of developing a tension/compression couple to transfer loads from the upper roof to the main roof for transverse displacements; all of the connections are pinned, and the struts are eccentric to both the horizontal and vertical centers of mass.
Reference: IBC Section 1604.4