| Date | Status | Code | Description | Ref | Location | Comments |
| 6/3/2022 | Transfer | Correct Below | * | | Kitchen | Will need to check appliances for listings, etc. |
| 6/3/2022 | Transfer | Correct Below | * | | Back of house Pantry 157. | Walk-in cooler not installed. |
| 6/3/2022 | Transfer | Correct Below | * | | Various - motorized shades. | 120V motorized shades do not have a listing mark. The UR mark is not the equivalent of a listing. |
| 6/3/2022 | Transfer | Correct Below | * | | Microturbine. | CEA written acceptance required. |
| 5/16/2022 | Corrected | Correct Below | * | | Lobby by restrooms. | Wall lighting panels not installed. |
| 5/16/2022 | Transfer | Correct Below | * | | Manual transfer switch. | If neutral is NOT switched, label service per 702.7(B). Label service per 702.7(A) to indicate portable generator connection point. Label per 702.7(C) to indicate type of generator that may be connected. Neutral not switched: "WARNING: FOR CONNECTION OF A NONSEPARATELY DERIVED (FLOATING NEUTRAL) SYSTEM ONLY." |
| 5/16/2022 | Transfer | Correct Below | * | | Service | 705.10 requires a directory denoting all alternate power source disconnecting means on premises. The directory needs to include both portable generator and microturbine disconnect locations. |
| 5/16/2022 | Transfer | Correct Below | * | | Microturbine. UPDATE ON GROUNDING COMMENTS. | 480V supply from microturbine to stepdown transformer - is this a separately derived system? Does it require a grounding electrode conductor connection? If no system grounding, engineer needs to explain. PER CAPSTONE VENDER: THE CAPSTONE IS A SEPARATELY DERIVED SYSTEM AND REQUIRES A GEC TO NEUTRAL BOND. THE "Y" CONNECTED TRANSFORMER SECONDARY CENTERPOINT IS NOT TO BE GROUNDED; IT DERIVES IT'S GROUND REFERENCE FROM THE SERVICE. |
| 5/16/2022 | Corrected | Correct Below | * | | Microturbine and 277/480V to 120/208V stepdown transformer. | Transformer as installed is Y - Y configuration. Transformer is different from the approved drawings. Engineer needs to approve the change. |
| 5/16/2022 | Corrected | Correct Below | * | | Microturbine. | Remove gas lines, any other obstructions from 110.26 working clearance area in front of electrical compartment. Existing curb is approx. 12in high and extends approx. 12in horizontally beyond the face of the electrical compartment. Working platform required to be extended to provide 3ft level space beyond the face of the electrical compartment. |