Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 706896
Inspection Type: Final Electrical
Inspector: M.Green
Result: Partial
Comment: Requested by: Tim Gorham 3506496 tgorham@alcanelectric.com | | Inspection covers all 3rd floor guest rooms. Some items remain to be corrected in 3rd and 4th floor guest rooms.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/8/2022TransferCorrect Below* 3rd and 4th floor "floating night stand."No listing mark on the product.
4/8/2022TransferCorrect Below* Room 342.Not complete - room has been used as a staging area.
3/25/2022CorrectedCorrect Below* Unit 430bathroom sink receptacle not functioning.
3/25/2022TransferCorrect Below* Near shower/bathroom at entry. Includes 3rd and 4th floor guest rooms.Readily accessible GFCI protection required for all receptacles within 6' of bathroom sink. See 210.8 (B)(5).
3/24/2022TransferCorrect Below* Guest rooms motorized shades. Includes 3rd and 4th floors.Sheet Note 5 requires a power connection to motorized shades. Are these installed at this time. Will need to verify proper equipment, etc. as part of inspection process.
3/24/2022TransferCorrect Below* Room 412.Drawings at MOA do not show this with (2) clothes washers and 240V dryers. Was this a change order?
3/24/2022TransferCorrect Below* Room AC units.Units labelled to require 15A OCPD.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS