Inspection #: 706635
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: Electrical final approved for remainder of 4th floor units excluding 442 and 430.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/25/2022TransferCorrect Below* Unit 430bathroom sink receptacle not functioning.
3/25/2022TransferCorrect Below* Near shower/bathroom at entry. Readily accessible GFCI protection required for all receptacles within 6' of bathroom sink. See 210.8 (B)(5).
3/24/2022TransferCorrect Below* Guest rooms motorized shades.Sheet Note 5 requires a power connection to motorized shades. Are these installed at this time. Will need to verify proper equipment, etc. as part of inspection process.
3/24/2022CorrectedCorrect Below* Guest rooms 3-panel screen separating sink from rest of room. Sheet Note 4 indicates an electrical connection to the screen for LED lighting. Will need to see this installed if electrical equipment. Also, will need to see to determine if GFCI protection is required for receptacle within 6ft.
3/24/2022TransferCorrect Below* Room 412.Drawings at MOA do not show this with (2) clothes washers and 240V dryers. Was this a change order?
3/24/2022CorrectedCorrect Below* Room 412 washer receptacles.210.8 requires all GFCI devices to be installed in a readily accessible location. NOTE: 2017 NEC does not require GFCI protection in non-dwelling unit laundry areas.
3/24/2022TransferCorrect Below* Room AC units.Units labelled to require 15A OCPD.