Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 696731
Inspection Type: Electrical Rough
Inspector: M.Green
Result: Partial
Comment: Requested by: Tim Gorham 3506496 tgorham@alcanelectric.com | | Electrical rough approved for the following areas: *1st floor corridor clouds. *1st floor "Tactic Room" walls and above sheetrock ceilings. *1st floor Lobby and Elevator Lobby walls and above sheetrock ceilings.. *1st floor workout room and adjacent corridor walls and above sheetrock ceilings. *1st floor"Engineering" office walls and above sheetrock ceilings. *1st floor Laundry and storage walls and above sheetrock ceilings. *3rd floor framed down sheetrock ceilings in guest rooms, halls and elevator lobby.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/25/2021Transfer01See inspection comments Microturbine-one line diagram, separately derived system. Grounding electrode conductor required.
10/25/2021Transfer01See inspection comments Service, microturbineVerify microturbine configuration with utility. Verify disconnecting means and requirement for having lockable disconnect. Labeling required for alternate source per 702.
10/25/2021Transfer01See inspection comments Service.Label AFC and date calculated.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS