Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 693418
Inspection Type: Electrical Rough
Inspector: V.Fosberg
Result: Partial
Comment: #8 bonding in pool room to rebar all metal surface locations to out of slab and 3/0 copper for turbine to metal electrode cadwelded on metal column at first floor at ceiling level by elevator,will be access hatch per contractor. electrical approved.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/25/2021Corrected01See inspection comments Microturbine-one line diagram, separately derived system. Grounding electrode conductor required.
10/25/2021Transfer01See inspection comments Service, microturbineVerify microturbine configuration with utility. Verify disconnecting means and requirement for having lockable disconnect. Labeling required for alternate source per 702.
10/25/2021Transfer01See inspection comments Service.Label AFC and date calculated.
10/22/2021Transfer01See inspection comments Location of branch circuit panel in pool equipment room. Drawings show panel in pool equipment room.2017 680.14(A) defines a pool equipment room as a corrosive environment and requires specific wiring methods. The pool room itself is also a corrosive environment. The panel will have to be isolated from corrosive atmospheres.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS