Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 680814
Inspection Type: Plumbing Rough
Inspector: J.Jaworski
Result: Correction
Comment: Water stacks containing rooms 317-328 and waste stacks containing 118 and 115, see corrections. NO SIGN OFF ON COVER. RE-INSPECT REQUIRED

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/7/2021CorrectedPlumbRgh14CommentsSee Inspectors Comments DWV support missing in each room serving the Lav. See section 313 in UPC for support requirements
9/7/2021CorrectedPlumbRgh14CommentsSee Inspectors Comments Hammer arrestors required in each room. Lavs, shower valves and WC
9/7/2021CorrectedPlumbRgh14CommentsSee Inspectors Comments per 707.4 cleanouts required at termination of building sewer. Each waste stack serving rooms above will require an accessible cleanout.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS