Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 679978
Inspection Type: Sprinkler Hydrostatic Test
Inspector: D.Meneses
Result: Partial
Comment: Please call Will prior to arrival. - 907.717.8477 - 3rd floor, west end only. Requested by: Chris Layfield 19072238441 clayfield@gmwfire.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/17/2021TransferFireSprkHydro2Partial Hydrostatic TestPartial approval for fire sprinkler system hydrostatic test for the following area(s): 4th floor, west half, Partial hydro.&nbsp; system was at 220 psi.&nbsp; There were no visible leaks at the time of this inspection.&nbsp;<div>Hydro test West half of 3rd Floor.&nbsp; Tested at 200 psi.&nbsp; All okay<br></div>
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS