Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 673971
Inspection Type: Plumbing Rough
Inspector: E.Wood
Result: Partial
Comment: Water rough-in and tests for rooms 115 thru 118, Approved. Heat piping and tests for rooms 115, 215, 315, 415, 117, 217, 317, 417, 118, 218, 318, 418, 120, 220, 320, 420, 121, 122, 222, 322, 422, 224, 324, 424, Approved. Condensate piping and tests for rooms 215, 315, 415, 217, 317, 417, 218, 318, 418, 220, 320, 420, 222, 322, 422, 224, 324, 424, Approved. Rain leader and tests for RD's and OD's at grids C x 1.7, F.6 x 1.7, and F.6 X 5, Approved. OK to wrap piping.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
       
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS