Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 656978
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Requested by: Tim Gorham 3506496 tgorham@alcanelectric.com | | Progress electrical final - 4th floor guest rooms 402 through 424, and Utility / Electric Room, and 412 Laundry.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/24/2022TransferCorrect Below* Guest rooms motorized shades.Sheet Note 5 requires a power connection to motorized shades. Are these installed at this time. Will need to verify proper equipment, etc. as part of inspection process.
3/24/2022TransferCorrect Below* Guest rooms 3-panel screen separating sink from rest of room. Sheet Note 4 indicates an electrical connection to the screen for LED lighting. Will need to see this installed if electrical equipment. Also, will need to see to determine if GFCI protection is required for receptacle within 6ft.
3/24/2022TransferCorrect Below* Room 412.Drawings at MOA do not show this with (2) clothes washers and 240V dryers. Was this a change order?
3/24/2022TransferCorrect Below* Room 412 washer receptacles.210.8 requires all GFCI devices to be installed in a readily accessible location. NOTE: 2017 NEC does not require GFCI protection in non-dwelling unit laundry areas.
3/24/2022TransferCorrect Below* Room AC units.Units labelled to require 15A OCPD.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS