Inspection #: 604233
Inspection Type: Final Plumbing
Inspector: E.Wood
Result: Correction
Comment: All else OK, see corrections. CCO until April 6, 2020.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/6/2020TransferPlumbFinalCommentsSee Inspector CommentsCoffee machines.Per the 2012 UPC 603.5.12 Potable water supply to beverage dispensers, carbonated beverage dispensers, or coffee machines shall be protected by an air gap, or a vented backflow preventer (vent ran to drain) in accordance with ASSE 1022.